Here are my suggestions about determining wall types:
Type 1 or A β 4 7/8β³ (Unrated) 1 Layer 5/8 GWB each side of 3 5/8β³ metal stud
- Use this as a wall between room β for example between two offices or classrooms.
- Same assemly as 1-HR rated wall β use 16β³ OC studs not 24β³ OC
- https://www.usg.com/content/usgcom/en/design-studio/wall-assemblies/assembly-detail.30128.html
Type 2 or B β 4 7/8β³ (1-HR) 1 Layer 5/8 GWB each side of 3 5/8β³ metal stud
- Same construction as the first wall type but with a 1 HR rating. Use this as the primary corridor wall or a wall enclose a group of spaces.
- Same assemly as unrated rated wall β use 16β³ OC studs not 24β³ OC
- https://www.usg.com/content/usgcom/en/design-studio/wall-assemblies/assembly-detail.30128.html
Type 3 or D β 6 1/8β³ (2-HR) 2 Layers 5/8 GWB each side of 3 5/8β³ metal stud
- This can be used to enclose fire rated stairs β except in taller buildings in NYC which must also be impact resistant. For this use an 8β³ Concrete Block.
- Use 16β³ OC studs not 24β³ OC
- https://www.usg.com/content/usgcom/en/design-studio/wall-assemblies/assembly-detail.30152.html
Type 4 or E β 9 1/2β³ Min β Size Varies as neededβ (1-HR) Chase Wall β 1 Layers 5/8 GWB oneside of 3 5/8β³ metal stud (4 1/4β³) β (then a 1β³ air space minimum for the chase) β and then a second 3 5/8β³ metal stud with 5/8β³ GWB (4 1/4β³) β Total 8 1/2 + 1β³ space min = 9 1/2β³ minimum
- This is used to run plumbing for water supply and drains. Toilet drains are 3β³ to 4β³ diameter depending on the number of toilets it supports. For a typical sink drain the pipe the pipe is 1 1/2β³. Walls of this kind are often covered by tile β which is considered a finish and not part of the wall type. It is also common to use βGreenboardβ or mold resistant GWB in wet conditions of this kind. In addition to the thickness of the drain pipe β clamps are required to hold the pipes in place and may require additional room.
- Some architects will run these pipes within the depth of the 3 5/8β³ stud and others prefer to leave a space between the metal studs for the drains. Minimum space between the studs is typically 1β³. This creates a wall of 9 1/2β³ and requires that the drain pipes be run partially within the thickness of the metal studs requiring the metal tracks to be cut. A better practice is to leave more than a 1β³ space so the pipes can run independently. For example leaving a 3 1/2β³ space will make the wall 12β³ (8 1/2β³ for studs and GWB + 3 1/2β³ = 12β³). Remember that pipes need room to turn and bend and they also need to be secured in place by clamps.
- I typically use 1β² to 1β²-2β³ face to face of GWB. The holes in slabs made for the pipes require firesafing.
- As the size varies as needed β In Revit I often make this using two different walls (each 1 layer 5/8β³ on 3 5/8β³ metal stud) and place this twice and adjust the distance between them β (I will demonstrate)
- Use 16β³ OC studs not 24β³ OC
- https://www.usg.com/content/usgcom/en/design-studio/wall-assemblies/assembly-detail.30109.html
Type 5 or F β 3 3/4β³ (2-HR) GWB Shaft Wall β 1 Layer 1β³ GWB Liner Panel β 2 1/2β³ CH Studs β 2 Layers 5/8β³ Firecode Type X GWB β 1 1/2β³ fireberglass insulation
- Use this for walls around elevator shafts & mechanical shafts. Can also be used around fire stairs (if they are not required to be impact resistant).
- This wall type uses the special CH metal stud that allows the wall to be installed from the outside.
- Use 16β³ OC studs not 24β³ OC
- https://www.usg.com/content/usgcom/en/design-studio/wall-assemblies/assembly-detail.30186.html
Type 6A or G1 -4 1/4β³ Furring β (Unrated) 1 Layer 5/8β³ GWB on 3 5/8β³ Metal Stud Frame
- Use this for unrated enclosures around columns or the inner wall of the facade.
Type 6B or G2 -4 7/8β³ Furring β (Unrated) 2 Layer 5/8β³ GWB on 3 5/8β³ Metal Stud Frame
- Use this for unrated enclosures around columns or the inner wall of the facade β when you need more durability.
- The construction can be used to achieve a 1 HR fire rating β but steel columns are better protected by spray on fireproofing
Type 7A or H1 -1 1/2β³ Furring β (Unrated) 1 Layer 5/8β³ GWB on 7/8β³ Metal Furring or Hat Channel
- Typically used when a GWB finish is being added to a solid concrete or concrete block wall.
- The channels are typically run horizontal and the extra room allows for the running of electrical
- https://www.clarkdietrich.com/products/furring-channel-hat-channel
Type 7B or H2 -2 1/8β³ Furring β (Unrated) 2 Layers 5/8β³ GWB on 7/8β³ Metal Furring or Hat Channel
- Same as above but more durable with an extra layer of GWB.
- https://www.clarkdietrich.com/products/furring-channel-hat-channel
Type 8 or J -7 5/8β³ actual (8β³ Nominal) (2-HR) Rated β Concrete block wall.
- Can be used to replace a shaft wall β and will be more impact resistant.
- https://ncma.org/resource/fire-resistance-ratings-of-concrete-masonry-assemblies/
- A solid concrete β poured in place wall an also be used (but is not a wall type but a detail)
Print this page
Leave a Reply