    Hisham and I have evaluated the beam you tagged and found that the beam section (12W x 24H) is insufficient to carry the load of the floor over a 24 foot span. We’ll design another beam section which is able to carry the floor load. Do you have any dimension restrictions? We can increase either the height or width (or both, if needed) but increasing height will be more efficient than width.